Anopol Effluent Plant and Ph Correction


Direct From Site Clearance
- Direct Site Clearance Price [?]
- £ 17,000 (+ VAT)
- Clearance ends
- 31 March 2021 16:00 GMT while stocks last
- Decommissioning,
Moving & Loading Contribution [?] - £ 3,000 (+ VAT) will be added to your invoice
- Part of a Direct Site Clearance
- Heatrae Sadia
- Condition
- From a working environment
- Location
- Norwich, Norfolk, UK
- Stock No
- HEA300
- Manufacturer
- Anopol
- Model
- Effluent Plant with Ph Correction
- Year of Manufacture
- 2010
- Serial
- 90905-111
- Condition
- From a working environment
- Other Info
- Average flow rate - 2000 litres per hour
- Location
- Norwich, Norfolk, UK
Description
Effluent Treatment Plant with Ph Correction
Designed to treat rinse waste water emanating from the pickling plant. The process flow diagram attached below indicates the principle of operation at time of installation. Please note some details may have changed in the interim period.
The final pH value of the water after treatment will be between 6.5 and 9.5
The complete system is composed of the following items:
Double Skinned Pipework
From Effluent Collector Tank to Effluent Storage Tank
2600 Litre Effluent Storage Tank to equalize flow
With 1 off Air Operated Double Diaphragm Pump for transfer to Neutralization Tank.
Lime Mixing System
Lime Preparation Tank with Stirrer
Dosing pump to Neutralization Tank.
Neutralization System
Neutralization Tank with Stirrer
Flocculent Preparation Tank with Stirrer
Outflow Pump for settler Loading
Dosing Pump for Flocculent Agent
Lamella Settlement and Sludge Tanks
A matched set originally manufactured by ERG Lancy. T8 Settlement is 3m x 2.34m x 3.6m high.
T10 Sludge is 3m x 1.5m x 2.5m high. Both tanks are mild steel painted and are fitted with a common inspection/maintenance platform complete with ladder and handrail.
Includes:-
- Pickling Plant Sump
- Waste Storage Tank (2600 Litres)
- Lime Reagent (2000 Litres)
- Neutralization Tank
- Polyflock Tank
- Final Discharge Tank
- Plc Monitoring Unit
- Waste Overflow
- Sludge tank
- Bund Drain
- Underground Waste Water Storage Sump
- Pickle Tank Sump
- Overflow from Treatment Tanks
- Settler Tank
- Fresh Water Storage Tank
Electrical Equipment
Switch Cabinet
Main Switch
Circuit Breakers
Safety Relays
Connection Terminals
PLC
pH Meter
Level Probes
Requires:
- Fresh Water Supply (Via Control Valve)
- Water Inlet - 1"
- Compressed Air - 6 bar
- Power - 3Kw
- Electrical requirement - 380 Volts, 3ph, 50hz
The process line is complete with a dedicated effluent treatment plant nominally as detailed in the schematic drawing above (when installed, current set up slightly adjusted).
Stage | Function |
1 | Pickling Plant Sump (in floor) |
2 | Waste Storage Tank (2600 litres) |
3 | Lime Reagent (2000 litres) |
4 | Neutralisation Tank |
5 | Polyflock Tank |
8 | Settlement Tank |
9 | Flow Buffer Tank |
10 | Sludge Storage Tank |
Print / Download Anopol Effluent Plant and Ph Correction Datasheet
Additional files
Photographs taken prior refurbishment. Our refurbishment service is not available on all machines.
Machines & equipment for sale
- Surface Treatment
- Cleaning & Degreasing
- Polishing & Belt Linishing
- Mass Finishing
- Ovens & Furnaces
- Process Cooling
- Shot Blasting
- Dust & Fume Extraction
- Air Compressors
- Rectifiers & Transformers
- Miscellaneous
- Latest Stock
- Special Offers
- Direct From Site Clearances
- Auctions
- Brand New Machines
- Available Immediately
- Sell Your Machine
Machine Alert
Get the latest machines emailed directly to you as they become available to buy online sign up