Transtherm Cooling Industries Limited Heavy Duty Adiabatic Air blast cooler

Stock No
CY590
Manufacturer
Transtherm Cooling Industries Limited
Model
TAFW 8
Year of Manufacture
2007
Serial
C-51477/1
New or Used
Used (Second Hand)
Ave. cooling capacity
500 kW
Ave. Water Flow Rate
13.28 Ltrs/Sec
Location
Our Central Warehouse, Aldridge, UK
External Dimensions (WxDxH mm)
6400 x 2700 x 1620mm

Description

Dry Air Blast Coolers

The Transtherm TAFW Adiabatic air blast coolers has been developed and built to give extremely reliable and robust performance and are designed for fast-track installation.

Air blast coolers offers an advanced level of energy saving and the highest efficiency ratings available. air blast coolers can be installed alongside an existing cooling system to provide a low cost, environmentally friendly method of free cooling.

Utilising air blast coolers to achieve Free Cooling is most effective for process applications requiring a higher set point of 10 -15oC+ or for low cost seasonal cooling in the winter months.

The units provide corrosion-free process fluid, operate at low costs, with no evaporation loss. The units have an anti-freeze facility for external units, as well as no water treatment costs and no chemical dosing resulting in low maintenance costs.

Air Blast Process Coolers - Re-circulating coolant passes through air blown heat exchange radiators where process heat is transferred to ambient.

Air Blast Radiator (Dry air cooler) - Hot water from the equipment to be cooled is pumped through a matrix of extended surface area tubes to maximise efficiency. Cool ambient air is induced (or forced) across the cooling matrix of the air blast radiator and is exhausted without any contact between the air and the water. Cooled uncontaminated water is then returned to the equipment to be cooled.

Self contained dry coolers are non-refrigerated cooling systems. They are an alternative to recirculating chillers for applications where precise temperature control and cooling below ambient temperature are not required. Typically, coolant will be delivered back to the process at approximately 10°C below ambient, however, this is variable dependent on process load and external conditions.

Free Cooling

Free Cooling is an economic method of utilising low external air temperatures to assist in chilling water, which can then be used for industrial processes or air conditioning.

Transtherms range of free cooling water chillers reduces electrical usage by utilising low ambient air temperatures to cool the return water whenever possible. 

The air blast cooler can be either integrated into an existing chiller circuit or as a ‘bolt on’ free cooler.  The free cooler enables the free cooling principle to be retro fitted to an existing unit/system. Once a unit/system is upgraded by the bolt on free cooler it will achieve all the associated advantages of free cooling and is an excellent option for clients wishing to reap the benefits of free cooling without investing in any replacement equipment.

The Adiabatic Chiller systems are built utilising the latest technology in the field of Adiabatic spray systems. The spray system is delivered by a variable speed DC pump which pressurises the nozzle at between 4 and 10 bar, dependant on load and ambient, to achieve the correct atomisation of the water.

As the nozzles are designed for an industrial piece of equipment they are easily cleanable by unscrewing, brushing and replacement of the nozzle. The stainless steel spray pipe work system does not corrode or oxidise over time but stays operational and aesthetically pleasing.

 

Technical Specification

Construction

Fins
Aluminium, 

Tube
electro-tinned copper 

Headers
Copper, 

Casing
2.5mm galvanised steel, 

Legs
80 x 80 x 3mm box section

Fans

Motor Insulation
8 x 1.5kW 

Stage control panel
4 stage fan controls with switchgear for a ‘plug and play’ solution

Common terminal box
Where controls are sited and bringing cabling for all fans to a common point

 

 

pdf icon Print / Download Transtherm Cooling Industries Limited Heavy Duty Adiabatic Air blast cooler Datasheet

Additional files

Photographs taken prior refurbishment. Our refurbishment service is not available on all machines.