skip to main content
Machines & equipment for sale

Climaveneta NECS W 0302 86 kW Water Cooled Process Chiller

Stock No
CV532
Manufacturer
Climaveneta
Model
NECS W 0302
Year of Manufacture
2011
Serial
32015694
New or Used
Used (Second Hand)
Ave. cooling capacity
86 kW
Ave. Water Flow Rate
14.9m3/h
Location
Our Central Warehouse, Aldridge, UK
Weight (kgs)
570kgs
External Dimensions (WxDxH mm)
1220 x 875 x 1500

Description

Climaveneta NECS W 0302 86 kW Water cooled process chiller  

Water to water indoor unit for the production of chilled/hot water with hermetic rotary Scroll compressors, braze-welded plate-type exchanger and thermal expansion valve.

External panels in pre-clad sheet steel and the structure in galvanised steel with an external paint finish. 

Precise and reliable operation

Premium efficiency, precision and reliable operation with all the working conditions are the key features of NECS-W units. All the components have been carefully selected and the algorithms have been specifically developed for these units, in order to ensure maximum reliability and meet the most challenging application requirements.

Complete versatility

NECS-W units are designed to fully satisfy any application or installation needs throughout a complete range of models, hydronic configurations and accessories. NECS-W is available in chiller mode (chilled water production), heat pump for hot water production (plus possible water side reversal)

High efficiency at partial

Climaveneta has designed NECS-W units with the goal of guaranteeing high efficiency at part load. The result achieved in the new single-circuit dual-compressor is an ESEER up to 6.01, equivalent to a 33% saving in seasonal energy consumption compared to traditional R-407C double-circuit unit.

W3000SE Compact controller

The W3000 electronic controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a complete LCD display, allowing the user to consult and intervene in the unit by means of a multi-level menu.

The regulation is based on the exclusive Quick Mind algorithm, including self-adaptive control logics, beneficial in low water content systems. The diagnostics includes a complete alarm management menu, with  “black-box” and alarm logging functions for enhanced analysis of the unit operation.

 Technical details

COOLING ONLY (GROSS VALUE)

Cooling capacity 86.7kW

Total power input 19.5kW

EER 4.45kW/kW

ESEER 5.13kW/kW

COOLING ONLY (EN14511 VALUE)

Cooling capacity 86.3kW

EER 4.23kW/kW
 

ESEER 5.13kW/kW

Cooling energy class D

EXCHANGERS

HEAT EXCHANGER USER SIDE IN REFRIGERATION

Water flow 14.9m³/h

Pressure drop 34.3kPa

HEAT EXCHANGER SOURCE SIDE IN REFRIGERATION

Water flow 18.2m³/h

Pressure drop 36.7kPa

REFRIGERANT CIRCUIT

Compressors nr. N°2

No. Circuits N°1

NOISE LEVEL

Sound Pressure dB(A)60

Sound power level in cooling dB(A)76

 

 

pdf icon Print / Download Climaveneta NECS W 0302 86 kW Water Cooled Process Chiller Datasheet

Photographs taken prior refurbishment. Our refurbishment service is not available on all machines.